Lenel Interface Module LNL-1320
Lenel Interface Module LNL-1320 – Dual Reader Access Control Interface Board
The Lenel Interface Module LNL-1320 (Dual Reader Interface or DRI module) is a commercial access control hardware component designed for the LenelS2 OnGuard platform. Serving as a bridge between an Intelligent System Controller (ISC) and door hardware, the Lenel Interface Module LNL-1320 supports full control for up to two access doors.
As shown in the product image, the board is constructed on a distinct red printed circuit board (PCB) equipped with removable screw terminal blocks, on-board configuration DIP switches, and diagnostic status LEDs. Operating over a 2-wire or 4-wire RS-485 communication bus, the Lenel Interface Module LNL-1320 allows integrators to locate reader interface panels up to 4,000 feet away from the central controller.
Key Features of the Lenel Interface Module LNL-1320
-
Dual Reader Capability: Connects up to 2 card readers, keypads, or biometric readers using Wiegand, Clock/Data, or RS-485 Open Supervised Device Protocol (OSDP) formats.
-
Flexible On-Board Power Regulation: Operates on 12 to 24 VDC power input and features an on-board voltage regulator supplying selectable 12 VDC or pass-through power (300 mA max per port) to connected readers.
-
Eight Supervised Inputs: Includes 8 alarm input zones configurable as normally open (NO), normally closed (NC), supervised (with End-of-Line 1 k Omega 1 k Omega resistor networks), or unsupervised for door contact and Request-to-Exit (REX) monitoring.
-
Six Form-C Relay Outputs: Equipped with 6 Form-C output relays (5 A @ 30 VDC) to control door strikes, magnetic locks, aux alarms, or visual indicators in fail-safe or fail-secure modes.
-
Offline Access Fallback: Supports offline facility-code access, lock, and unlock modes to ensure secure door operation if communication with the host controller is temporarily interrupted.
-
Advanced Security Encryption: Supports AES 128-bit or 256-bit encryption along with OSDP Secure Channel protocols for secure data transmission.
Common Applications and Industrial Usage
The scalability and interface options of the Lenel Interface Module LNL-1320 make it suitable for high-security facilities:
-
Enterprise Door Access Control: Regulates single-door or dual-door entry points, managing electric strikes, door position sensors, and local exit request buttons.
-
Turnstile & Barrier Gate Management: Interfaces card readers and direction-control relays for pedestrian turnstiles and vehicle parking gates.
-
Biometric & High-Security Verification: Communicates with modern OSDP biometric readers, enabling remote biometric template download and encrypted communication directly to OnGuard servers.
-
Cabinet & Equipment Monitoring: Dedicated secondary input circuits monitor cabinet tamper switches and UPS power fault states.
Technical Specifications
The electrical limits, mechanical dimensions, and system boundaries of the Lenel Interface Module LNL-1320 conform to access control standard UL 294:
| Parameter Specification | Technical Details & Operational Values |
| Component Classification | Dual Reader Interface (DRI) Access Control Board |
| Primary Target Keyword | Lenel Interface Module LNL-1320 |
| Operating Input Voltage | 12 to 24 VDC pm 10% |
| Current Consumption | 550 mA max @ 12 VDC / 330 mA max @ 24 VDC (plus reader load) |
| Upstream Communication | RS-485 (2-wire or 4-wire) multi-drop bus up to 4,000 ft (1,219 m) |
| Supported Card Formats | Supports up to 16 card and asset formats |
| Reader Interface Formats | Wiegand (Data1/Data0), Magnetic (Clock/Data), Supervised F/2F, OSDP RS-485 |
| On-Board Inputs | 8 General Supervised/Unsupervised (1 k Omega EOL) + 2 Dedicated Tamper/Power |
| Relay Outputs | 6 Form-C Contacts (5 A @30 VDC) |
| Operating Temperature | 0°C to +70°C (32°F to 158°F) |
| Physical Dimensions | 152 mm x 203 mm x 25 mm (6″x 8″ x 1″) |
| Regulatory Compliance | UL 294, UL 1076, CE, FCC Part 15, RoHS |
Installation Guidelines and Best Practices
Installation Note: Turn off all main DC supply power before setting hardware DIP switches or inserting wire terminals onto the board.
Setting Addressing DIP Switches: Configure the 8-position DIP switch block to set the unique RS-485 board address (0–31) and host communication baud rate (9,600 to 38,400 bps).
Wiring Supervised Inputs: Wire door contact and exit request lines using 1 k Omega End-of-Line (EOL) resistors in series/parallel to allow the board to detect open, short, and tamper states.
Shielded Cable Grounding: Use 24 AWG shielded twisted-pair cabling for the RS-485 communication line, grounding the drain wire at one end to prevent electrical noise interference.
To review official access control board datasheets, wiring schematics, and complete OnGuard system hardware guides, check the global LenelS2 Access Solutions Directory.