FERRAZ SHAWMUT TIME DELAY FUSE ATQR30
FERRAZ SHAWMUT TIME DELAY FUSE ATQR30 – Industrial Amp-Trap 2000® Class CC Power Fuse
The FERRAZ SHAWMUT TIME DELAY FUSE ATQR30 (Mersen / Ferraz Shawmut Amp-Trap 2000® series, catalog number ATQR30 / F200864) is a high-performance Class CC current-limiting fuse specifically engineered for maximum protection of control transformers, solenoids, and inductive loads. Designed to withstand high magnetizing inrush currents without nuisance opening, the FERRAZ SHAWMUT TIME DELAY FUSE ATQR30 delivers dependable branch-circuit overcurrent protection.
As shown in the product image, the fuse utilizes a high-grade fiberglass body construction fitted with bright tin-plated copper ferrule caps and an iconic Class CC rejection tip. Rated at 30 A (600 VAC), it provides exceptional current-limiting capabilities to protect downstream electrical components against extreme short-circuit fault conditions.
Key Features of the FERRAZ SHAWMUT TIME DELAY FUSE ATQR30
-
Optimized Inrush Time-Delay: Specifically engineered with exceptional time-delay characteristics to easily absorb high magnetizing inrush currents from control transformers and motor starters.
-
Extreme Current Limitation: Operates fast under severe short-circuit conditions to significantly limit peak let-through current and fault energy, preventing equipment damage.
-
Rejection-Style Class CC Design: Features a specialized rejection tip on the ferrule cap to prevent accidental replacement with lower-rated supplemental fuses.
-
High Interrupting Rating: Delivers a 200,000 A RMS symmetrical interrupting rating at 600 VAC, making it suitable for high fault-current capacity networks.
-
Durable Fiberglass Body: Constructed with a high-density, dimensional-stability fiberglass body that ensures reliable electrical performance under demanding thermal conditions.
-
Global Safety Certifications: Meets UL 248-4 (Class CC Standards), CSA Certified C22.2 No. 248.4, and CE guidelines.
Common Applications and Industrial Usage
The specialized current-limiting and time-delay characteristics of the FERRAZ SHAWMUT TIME DELAY FUSE ATQR30 make it a top choice for commercial and industrial control applications:
-
Control Transformer Primary Protection: Protects primary power circuits on control transformers that experience extreme magnetizing current spikes upon energization.
-
Inductive Load Circuits: Shields solenoids, contactors, and electromagnetic holding coils against overcurrent and short-circuit faults.
-
Industrial Control Panels (UL 508A): Serves as compact main branch or sub-branch circuit protection in space-constrained industrial automation and control enclosures.
-
HVAC & Motor Controllers: Protects branch motor circuits, rooftop HVAC units, air compressors, and small motor controllers against fault-current damage.
Technical Specifications
The electrical limits, physical dimensions, and operational characteristics of the FERRAZ SHAWMUT TIME DELAY FUSE ATQR30 comply with standard Class CC specs:
| Parameter Specification | Technical Details & Operational Values |
| Component Classification | Amp-Trap 2000® Class CC Time-Delay Power Fuse |
| Primary Target Keyword | FERRAZ SHAWMUT TIME DELAY FUSE ATQR30 |
| Manufacturer Catalog / Reference | Mersen (Ferraz Shawmut) ATQR30 / F200864 |
| Amperage Rating | 30 A |
| Voltage Ratings | 600 VAC / 300 VDC |
| AC Interrupting Rating (AIR) | 200,000 A RMS Symmetrical @ 600 VAC |
| DC Interrupting Rating | 100,000 A @ 300 VDC |
| Time-Delay Characteristics | Minimum 12 seconds @ 200% rated current |
| Body Material / Terminal Caps | High-Density Fiberglass / Tin-Plated Copper Ferrules |
| Physical Dimensions | Diameter: 10.3 mm (13/32″) x Length: 38.1 mm (1-1/2″) |
| Terminal / Mount Style | Ferrule / Class CC Rejection Feature |
| Direct Cross-References | Littelfuse KLDR030, Bussmann FNQ-R-30 |
Installation Guidelines and Best Practices
Safety Precaution: Isolate and de-energize main supply breakers before inspecting, inserting, or replacing branch power fuses.
Rejection Holder Compatibility: Install only in UL-approved Class CC rejection-style fuse blocks or finger-safe DIN-rail fuse holders (such as Mersen USCC series).
Transformer Sizing Rules: Follow NEC Article 450 guidelines when sizing control transformer primary protection—typically sizing ATQR fuses at 300% to 500% of primary full-load current (FLA).
Visual Verification: Ensure the rejection tip seats fully inside the rejection slot of the fuse block to guarantee a firm, low-resistance connection.
To review official class CC time-delay fuse curves, rejection dimensions, and complete Amp-Trap catalog specifications, consult the global Mersen Electrical Circuit Protection Directory.
To evaluate real-time regional warehouse stock availability or request commercial quotes for bulk procurement needs, please connect with our sales branch via the Control Qatar Contact Page.