DETUNED REACTOR LVR07500A40G SCHNEIDER
DETUNED REACTOR LVR07500A40G SCHNEIDER – Low-Voltage Power Quality & Anti-Harmonic Protection
The DETUNED REACTOR LVR07500A40G SCHNEIDER (from Schneider Electric’s PowerLogic / VarSet PFC range) is a heavy-duty, three-phase anti-harmonic detuned reactor designed to protect power factor correction (PFC) capacitors from harmonic resonance and thermal overload. In modern electrical networks dominated by non-linear loads—such as variable speed drives (VFDs), uninterruptible power supplies (UPS), and LED lighting—harmonics can distort line voltage and cause premature capacitor failure.
The DETUNED REACTOR LVR07500A40G SCHNEIDER is connected in series with PFC capacitor banks to form a tuned LC circuit. Tuned specifically to a 7% relative impedance factor (190 Hz tuning frequency 3.8 tuning order at 50 Hz), it prevents harmful harmonic amplification and ensures long-term operational safety across commercial and industrial distribution networks.
As depicted in the product image, the reactor features vertical high-grade copper/aluminum windings mounted on a low-loss laminated steel core, fitted with labeled terminal pads (A-A1, B-B1, C-C1) and an integrated thermal protection microswitch.
Key Features of the DETUNED REACTOR LVR07500A40G SCHNEIDER
-
Effective Anti-Harmonic Attenuation: Designed with a 7% detuning factor (190 Hz) to shift the LC resonant frequency safely below the 5th (250 Hz) and 7th (350 Hz) dominant network harmonics.
-
High Thermal & Overload Endurance: Constructed with Class H electrical insulation, supporting continuous operation up to 1.2 x I_n fundamental current and high harmonic current spectra (38.2% on 5th harmonic).
-
Integrated Thermal Microswitch Protection: Equipped with an internal thermal contact trigger (2 AÂ / 250V AC) that trips the main PFC contactor or triggers an alarm if internal winding temperatures exceed normal limits.
-
Low Loss Vertical Winding Design: High-efficiency core construction minimizes operational I2RÂ power losses (maximum 320 WÂ heat loss) while maximizing heat dissipation via natural or forced air convection.
-
Rugged Pad Terminals: Heavy-duty flat copper pad connectors allow secure bolt connections to power busbars or high-gauge cable lugs.
Common Applications and Industrial Usage
The robust construction and precise inductance value of the DETUNED REACTOR LVR07500A40G SCHNEIDER make it an essential component in heavy industrial power quality systems:
-
Automatic Capacitor Banks (PFC Panels): Installed inside low-voltage automatic power factor correction switchboards to safely deliver $50\text{ kvar}$ reactive power compensation.
-
Industrial Facilities with VFDs & Inverters: Protects electrical distribution transformers and power factor capacitors in manufacturing plants heavily equipped with motor drives.
-
Data Centers & Commercial Infrastructure: Stabilizes line voltage, reduces total harmonic distortion (THDi), and prevents neutral current overload in IT facilities and office towers.
Technical Specifications
The core electrical, mechanical, and thermal specifications for the DETUNED REACTOR LVR07500A40G SCHNEIDER are detailed below:
| Parameter Specification | Technical Details & Operational Values |
| Component Classification | Three-Phase Anti-Harmonic Detuned Reactor |
| Primary Target Keyword | DETUNED REACTOR LVR07500A40G SCHNEIDER |
| Manufacturer / Range | Schneider Electric / PowerLogic PFC Series |
| Rated Reactive Power Output | 50 kvar at 400V AC, 50 Hz |
| Rated Operating Voltage (U_n) | 400 V AC\ (50 Hz) |
| Detuning Factor / Order | 7% Relative Impedance /190 Hz (3.8 Tuning Order) |
| Nominal Inductance (L) | 0.75 mH\ (pm 5%Â tolerance) |
| Fundamental Current Rating (I_1) | 72.2 AÂ RMS |
| RMS Total Current Rating (I_rms) | 77.9 AÂ RMS |
| Maximum Losses | le 320 WÂ at full rated load |
| Insulation Class & Test | Class H (180°C) / Dielectric 4 kV (50 Hz, 1 min) |
| Terminal Connection Type | Heavy-Duty Flat Pad Terminals |
| Dimensions (H x W x D) | Approx. 270 x 260 x 200 mm |
| Product Net Weight | Approx. 22.0 kg |
| Operating Temperature / IP | 0°C to +55°C / IP00 Open Frame |
Installation Guidelines and Best Practices
SAFETY NOTICE: Ensure the power factor correction panel is fully de-energized and capacitors are discharged prior to installation or maintenance.
Thermal Ventilation: Mount the DETUNED REACTOR LVR07500A40G SCHNEIDER in the lower section of PFC enclosures with forced fan convection to effectively exhaust internal heat.
Thermal Switch Wiring: Connect the internal thermal contact wire directly into the control circuit of the associated step contactor to disconnect the capacitor step during overheating conditions.
Terminal Torque: Tighten busbar connections securely to recommended torque specs to maintain low electrical contact resistance.